【Name】:AB-G60 cable fire retardant coating
1 : Use
It is used in the fireproof and fire retardation protection of all kinds cable with different voltage grade. Mainly used in fireproof protection of electricity plant, transformer station,petroleum, chemical, construction and communication etc..
 

2 : Technical Characteristics
AB-G60 cable fire retardant coating has excellent heat insulation properties, strong adhesion, good flexility and resistance to water, oil, salt water and weather.
 

3 : Technical Indexes
Item
Index
Flame retardant property(m)
Charring height 0.46
Appearance
No caking, white think liquid
Fineness(µm)
≤90
Drying Time
Surface/h
≤2
Whole/h
≤8
Oil resistance/d
Soak for 7 days, no shrinking or drops
Salt resistance /d
Soak for 3 days, no shrinking or drops
Resistance to wet heat/d
Soak for 7 days, no shrinking or drops
Resistance to cold and heat periodicity/time
After 15 circulation,no bubble or drops
Bending resistance
No shrinking or drops

4 : Constructional parameters
Use level of coating/g/m2
300-330
Thickness of coating film mm
0.20-0.22
Painting alternation/h
≥10
Coating times
5
Coating method
Brush coating or spray coating
Thinner
xylene or 200# solvent oil
Diluted amount
0-3%
 

5 : Packaging and storage
Packed in metal pail, 20l per pail, stored in draughty and dry place. , quality guarantee period: 1 years.